极空 BMS-CAN 通信协议 V1.02

极空官方资料全文,共约 8009 字。内容版权归成都极空科技有限公司所有,本站作为授权经销渠道整理提供,仅供参考,以厂家最新有效文件为准。

及空 J I K 0 N G The file number The page code Page 1 of 5 The version number VI. 02 Effective date 20190428 version instructions note V101 Original version, standard frame format V102 Increases the cumulative discharge timing BMS-CAN communication protocol

1 overview This protocol specifies the communication protocol between the BMS and other nodes in the automotive CAN network. 2 Definition of Terms BMS: Battery Management System. Can: Controller Area Network; 3 Physical interface This agreement adopts CAN2.0A standard, and the frame format adopts standard frame.Communication baud rate is 250kbps.

The communication between the BMS and the instrument is point-to-point one-way communication, that is, the BMS sends data to the instrument, and the instrument only receives and interprets the data for display. 4 Data convention In the data transmission of this protocol, low-byte first-send mode (small-end) is adopted for multi-byte data, except for

special instructions. For the battery's total current value, a positive value indicates discharge and a negative value indicates charge. The data format of this Agreement is defined as follows: CANJD Data fields FUNC SA DATA 3 8 0 ~ 64 Func is the function code that represents the frame data type.

SA is the source address, here represents the address of the BMS, fixed as 0xF4. Data refers to DATA domain information, and the frame length of this protocol is fixed at 8 bytes. 及空 J I K 0 N G The file number The page code Page 2 of 5 The version

number VI. 02 Effective date 20190428 Parameter group number The parameter group number is assigned as follows: The serial The name of the describe FUNC ID The sender Message cycle 1 BATT ST Battery status information 0x02 0x02F4 BMS 20ms 2 CELL VOLT Batteries voltage 0x04 0x04F4 BMS 100ms

3 CELL TEMP The cell temperature 0x05 0x05F4 BMS 100ms 4 ALMJNFO The alarm information 0x07 0x07F4 BMS 100ms Messages of battery status, cell voltage and cell temperature are sent periodically after power on, and alarm message is event contact

Heuristic sending. 6 Message Definition 6.1 Battery Status (BATT ST) ID: 0x02F4 This message defines power battery status information. The specific format is as follows: The serial parameter Start bit A length of The scope of The resolution of

The offset unit note 1 BattVolt 0 16 0 ~ 1000 0.1 0 V Total voltage of battery pack2 BattCurr 16 16 - 400 ~ 1000 0.1 - 400. A Total battery current 3 SOC 32 8 0-100. 1 0 % The residual capacity 4 DischgTime 48 16 0 ~ 65535 1 0 h Discharge time

02F4 13 01 D7 11 33 XX 64 00 Represents: voltage 27.5V, current 56.7A (precision: 0.1A), SOC51%, discharge time 100h. 6.2 Cell voltage (CELL_VOLT)ID: 0x04F4 This message defines the cell voltage information. The specific format is as follows:

The serial parameter Start bit A length of The scope of The resolution The offset unit note 1 MaxCellVolt 0 16 0 ~ 5000 1 0 mV Maximum cell voltage 2 MaxCvNO 16 8 1-250. 1 1 Highest monomer position3 MinCellVolt 24 16 0 ~ 5000 1 0 mV Minimum cell voltage

4 MinCvNO 40 8 1-250. 1 1 Lowest cell position For example: 04F4 8C 0A 05 92 09 08 XX XX Represents: the highest cell voltage is 2700mV, corresponding cell number is 5;The lowest cell voltage is 2450mV, and the corresponding cell number is 8.

及空 J I K 0 N G The file number The page code Page 3 of 5 The version number VI. 02 Effective date 20190428 6.3 Cell temperature (CELL_TEMP)ID: 0x05F4 This message defines the cell temperature information. The specific format is as follows: The

serial parameter Start bit A length of The scope of The resolution The offset unit note 1 MaxCellTemp 0 8 - 50 ~ 200 1 - 50 ° c. Maximum cell temperature2 MaxCtNO 8 8 1-250. 1 1 Maximum temperature position3 MinCellTemp 16 8 - 50 ~ 200 1 - 50 ° c. Minimum cell

temperature4 MinCtNO 24 8 1-250 1 1 Lowest temperature position5 AvrgCellTemp 32 8 - 50 ~ 200 1 - 50 ° c. Average cell temperature For example: 05F4 48 06 2F 01 3F XX XX XX Represents: the highest cell temperature is 22°C, corresponding cell number is 6;The minimum cell temperature is -3°C,

corresponding cell number is 1.Average cell temperature is 13 °C. 6.4 Fault information (ALM_INFO) ID: 0x07F4 The alarm message is sent by event trigger. When there is an alarm, BMS sends the message periodically. If there is no alarm message, it will not be sent.When multiple alarms occur at the same time, the alarm number will be displayed circularly on the

instrument interface, up to 4 alarm numbers can be displayed circularly.The alarm number is shown in the order of alarm occurrence as priority. The specific format is as follows: Alarm no. parameter Start bit A length of The scope of The resolution of

The offset unit note 1 Monomer overvoltage 0 2 0 ~ 3 1 0 The alarm level 2 Monomer undervoltage 2 2 0 ~ 3 1 0 3 Total voltage overvoltage 4 2 0 ~ 3 1 0 4 Total voltage undervoltage 6 2 0 ~ 3 1 0 5 The pressure difference of 8 2 0 ~ 3 1 0 6 Discharge flow 10 2 0 ~ 3 1 0

7 Charging flow 12 2 0 ~ 3 1 0 8 The temperature is too high 14 2 0 ~ 3 1 0 9 The temperature is too low 16 2 0 ~ 3 1 0 10 Temperature difference is too large 18 2 0 ~ 3 1 0 11 SOC is too low 20 2 0 ~ 3 1 0 12 Insulation is too low 22 2 0 ~ 3 1 0

13 High voltage interlock fault 24 2 0 ~ 3 1 0 14 External communication 26 2 0 ~ 3 1 0 15 Internal communication 28 2 0 ~ 3 1 0 Alarm level: 0 for no alarm, 1 for serious alarm, 2 for important alarm, 3 for general alarm 07F4 43 00 20 00 XX XX XX XX

Represents: monomer overpressure, level 3 alarm;Total voltage undervoltage, level 1 alarm;Too low SOC, level 2 alarm. 及空 J I K 0 N G The file number The page code Page 4 of 5 The version number VI. 02 Effective date 20190428 7 Test cases 7.1 Normal state

Normal state only displays SOC, voltage value, hour meter and other information.In normal state, only battery status message, cell voltage message and cell temperature message are sent, and no alarm message is sent. CANJD data Data meaning The instrument shows

0x02F4 13 01 D7 11 33 XX 64 00 Voltage 27.5V, current 56.7A, SOC51%, discharge time 100h The main interface displays the voltage of 27.5, the SOC display of 51%, the quantity grid is 2 grids, and the current is not displayed 7. 2 Low battery

When the electric quantity is too low alarm (SOCX20%) occurs, the main interface does not display the voltage, but displays the current alarm number. If it is a single alarm, the corresponding cell number of the single alarm will be displayed at the hour meter.

CANJD data Data meaning The instrument shows 0x02F4 El 00 8A 10 10 XX XX XX Voltage 22.5V, current 23.4 A, SOC was 16% The alarm number 11 is displayed on the main interface, and the "AL "symbol flashes at the same time.SOC displays 16%, power

grid is 1, current is not displayed 0x07F4 00 00 30 00 XX XX XX XX Too low SOC 3 level alarm 7.3 Excessive and low monomer voltage CANJD data Data meaning The instrument shows 0x04F4 8C 0A 05 92 09 08 XX XX Maximum monomer voltage 2700mV, The corresponding cell number is

5;The lowest one Body voltage 2450mV, The alarm number 1 and 2 are displayed on the main interface, and the "AL" symbol flashes.The cell numbers 5 and 8 corresponding to the alarm are displayed at the hour meter 0x07F4 OF 00 00 00 XX XX XX XX Single overpressure level 3 alarm

single underpressure level 3 alarm 7.4 Cell temperature is too high and too low CANJD data Data meaning The instrument shows 0x05F4 48 06 2F 01 3F XX XX XX The maximum temperature of the cell is 22°C, and the corresponding cell number is 6.The minimum cell temperature

is -3°C, corresponding cell number is 1.Average cell temperature is 13°C The alarm number 8 and 9 are displayed on the main interface, and the "AL" character number flashes.The cell numbers 6 and 1 corresponding to the alarm are displayed at the hour meter

0x07F4 00 CO 03 00 XX XX XX XX Monomer over temperature level 3 alarm monomer low temperature level 3 alarm And empt y J I K 0 N G The file number The page code Page 5 of 5 The version number VI. 02 Effective date 20190428